Family owned and operated Australian company

My Quotes
X
  • No products in the list

F2” FUEL OVERFILL VALVE

Select Options

Product price
Additional options total:
Order total:
SKU 801904014 Category

APPLICATION

  • Valve to avoid a fuel spill because of an excessive filling of the aerial tanks.
  • It is installed in the filling tank ho.e. This valve closes the liquid flow when the product level gets almost its capacity total, using a buoy and a Venturi jet system, causing some hose strokes and a flow reduction which means the supply must be cut.
  • The lower valve diameter is intended for the 2” discharge pipes.
  • It has included a special key for an easy installation.

 

OPERATION

  • This valve is designed to close the fuel pass when its level is around 203 mm from the tank capacity.
  • Then a small bypass valve will allow emptying the hose with a flow of 19 l/min until the liquid level gets 76 mm of the tank capacity. The bypass valve completely closes the fuel pass.

F2” OVERFILL VALVE
Scroll to Top

Contact us